• 匿名
点击 485回答 1 2012-03-09 18:13

5 cube meter diesel tank leakage-proof measures

已解决 悬赏分:0 - 解决时间 2012-04-15 12:46
 one question need your help.
there is a 5 cube meter diesel tank in our factory,  it is installed on the floor with leakage-proof measures in a isolated room, but the fire prevention agency ask us to install it under ground.
and told us it is enssential and legal requirement? how can i get the legal requirements? could you help me?
反对 0举报收藏 0评论 0
最佳答案
  • 匿名
支持 0 反对 0 举报 2012-03-18 11:03
 As per the national code concerned ( GB50074-2002), it's not recommended of using underground type for the oil tank design on the condition that there is any SPECIAL REQUIREMENTS .....on the contrary, they suggest using over ground type.However,it's also not mandatory clause.
 
Here is some clauses available for your information.
“6.0.1 石油库的油罐设置应采用地上式,有特殊要求时可采用覆土式、人工洞式或埋地式。
...
1 甲、乙类油品的储存量,不应大于车间2d的需用量,且不应大于2m3
2 丙类油品的储存量不宜大于10m3
5 存油量不大于5m3的丙类油品储罐(箱),可直接设置在丁、戊类生产厂房内的固定地点。
  6 油罐的通气管管口应设在室外。甲、乙类油品储罐的通气管管口应高出屋面1m,与厂房门、窗之间的距离不应小于4m。”
 
As we know there are at least two kinds of diesel oil under use, one is so called Light Diesel oil and another is Heavy Diesel oil.  According to fire risk classfication clauses,light diesel oil belongs to type 乙 but heavy diesel oil remains with type 丙. So it's recommended to check the oil type used in prior any actions.